Switchboard
UL891 /CSA C22.2 No.244
Professional OEM/ODM Customization Solutions
product-main

Switchboard

share

Facebook
Twitter
LinkedIn
Product Introduction

The switchboard is a core equipment in power systems for centralized distribution, control, and protection of electrical energy. It is widely used in industrial plants, commercial buildings, residential complexes, data centers, public facilities, and other scenarios.It adopts premium composite galvanized plates and stainless steel materials. Internally, it integrates circuit breakers, contactors, fuse protection devices, and supports multi-circuit power distribution. It possesses multiple protection functions such as overload, short circuit, temperature rise, and leakage current protection, ensuring power system safety.With remote operation and a modular structure design, it facilitates expansion and maintenance, meeting different users’ diversified power management requirements.

Product Features
UL Listed Certification – Code Compliance and Safety Assurance
Designed and manufactured in full compliance with UL 891. All required type tests including temperature rise, dielectric withstand, and short‑circuit current rating (SCCR) -are successfully performed. UL Listing is mandatory for legal sale and installation in the U.S. and Canadian markets.
Dead-Front Construction -Enhanced Operator Protection
All energized parts are fully enclosed within the metal cabinet; the front face has no exposed live conductors. This design prevents accidental contact and complies with NFPA 70E safe work practices.
High Continuous Current and Short‑Circuit Withstand Capability
Main bus bar is rated up to 6000 A continuous, with a short‑circuit withstand rating up to 200 kA. Available with fixed or draw‑out circuit breakers equipped with electronic trip units (LSI and LSIG protection) to accommodate high‑capacity distribution systems.
Modular Platform -Flexible Configuration
Built on an open modular architecture, allowing optional integration of digital meters, power monitoring, surge protective devices (SPD), and Modbus communication ports. Offers a wide range of options including copper or aluminum bus bars, front‑access or front‑and‑rear‑access configurations.
Indoor and Outdoor Versatility
Available with NEMA 1 (indoor) and NEMA 3R (rain-tight, outdoor) enclosures to suit various installation sites. The switchboard is seismic‑qualified per IBC and OSHPD certification standards.
Cost-Effective and Broadly Applicable
Offers a significantly lower manufacturing cost compared to UL 1558 metal‑enclosed switchgear, making it a highly cost‑effective solution for most general distribution applications. The standardized design simplifies field installation and reduces overall construction time.
process5
Product Image Display
Low Voltage Distribution System
Basic PDU Socket
Switchboard Technical Selection Table (Core Technical Parameter Selection Table for LV Switchboards )
Dimension UL 891 Standard  Technical Options IEC 61439-1/2 Standard  Technical Options
Standards UL 891, CSA C22.2 No. 244, NEC (NFPA 70), IEEE IEC 61439-1/2, IEC 60364,  IEC 60909, IP Ratings
Rated Voltage 600V, 480V, 415V, 380V, 240V, 208V (Up to 1000V DC/AC)
Rated Current 1000A, 1200A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, 6000A 1000A, 1250A, 1600A, 2000A, 2500A, 3150A/3200A, 4000A, 5000A, 6300A, (Customized up to 8000A)
Frequency 50Hz / 60Hz  (Universal Global Frequency (50/60Hz) compatible.)
System Type 3-Phase 3-Wire (3P3W) / 3-Phase 4-Wire (3P4W)  (Optional Neutral Bus (Configurations available with or without neutral).
SCCR & Icw 65kA, 85kA, 100kA, 150kA, 200kA (@415V/480V) 50kA, 65kA, 85kA, 100kA, 150kA (@415V/480V)
Busbar Material Tin-plated/Silver-plated Copper (Standard Tin-Plated or Silver-Plated Finish for superior oxidation resistance.)
Enclosure Rating NEMA 1  NEMA 3R , NEMA 4X IP54, IP65
Dimensions (H×W×D) Variable Enclosure Dimensions optimized for different current ratings.
Cable Entry Customizable Top and Bottom Cable Entry or Exit for flexible installation.
Enclosure Material High-quality Galvanized Steel Sheet.  /  SS304 Stainless Steel
Breaker Brand Schneider, ABB, Eaton, Siemens,LS, Noark, or KAILES Standard
Smart Monitoring Smart Power Meter with Harmonic Analysis & Modbus/TCP Communication
Installation Guide

UL 891 Switchboard: NEC 110.26 Installation Compliance Requirements

1:Front Working Space Depth

This is the most stringent standard. Per NEC Table 110.26(A)(1), for 0-600V systems, the depth requirements are as follows:

Condition 1 (Insulated Wall Opposite): Minimum 3 ft (0.91 m).

Condition 2 (Grounded Metal/Concrete Opposite): Minimum 3.5 ft (1.07 m).

Condition 3 (Energized Equipment Opposite): Minimum 4 ft (1.22 m).

2:Width of Working Space

The width must be equal to the width of the equipment or at least 30 inches (0.76 m), whichever is greater. All doors must be able to open at least 90 degrees.

3:Headroom

A minimum vertical clearance of 6.5 ft (approx. 2 m) from the floor is required. If the equipment is taller than 2 m, the headroom must match the equipment height.

4:Egress / Access to Working Space

Mandatory for large equipment (1200A or more, width over 6 ft):

Dual Egress: One entrance/exit is required at each end of the working space.

Panic Hardware: Exit doors must open outward and be equipped with a Panic Bar for rapid evacuation in the event of an arc flash incident.

5:Dedicated Electrical Space

The space above the switchboard to the ceiling (or within 6 ft) is the dedicated electrical space. It is strictly prohibited to install foreign systems such as water pipes, HVAC ducts, or sprinklers in this zone.

6:Rear Clearance

Rear Access Models: Rear clearance must match front requirements (3-4 ft).

Front Access Only Models: Wall-mounting is permitted, but 1-2 inches of clearance is recommended for air circulation.

switchboard (1)
KAILES: One-Stop Service System from Design to Global Delivery
Certification Certificate
Frequently Asked Questions
Experiential Marketing
Q: Which standards do your switchboards comply with?
We provide units fully compliant with UL 891 (USA), CSA C22.2 No. 244 (Canada), and IEC 61439-1/2 (International) standards.
Q: Can I specify the brand of circuit breakers?
Yes. We support integration with global leading brands such as Schneider, ABB, Eaton, and Siemens.
Q: What is the typical lead time?
Standard models typically take 8-10 weeks. Complex multi-bay systems take approximately 12-14 weeks depending on customization.
Q: Is cable entry customizable?
Yes. We offer customizable Top, Bottom, or Side cable entry to match your onsite wiring requirements.
Q: What material is used for the busbars?
We use 99.9% high-purity electrolytic copper, standard with Tin-plating or Silver-plating for superior oxidation resistance.
Q: What are the space requirements for installation?
Per NEC 110.26, we recommend 48" (1.2m) of front clearance and 40" (1m) for rear maintenance access.
Q: What is your warranty period?
Our standard warranty is 12-24 months from the date of shipment, with extended warranty options available.
Q: How do you provide support in case of a fault?
We provide 24/7 remote technical support. If components need replacement, we ship via global express and provide video-guided installation support.