A low-voltage panelboard is designed for centralized distribution and protection of feeder and branch circuits. It is widely used in commercial buildings, industrial facilities, data centers, residential projects, and public infrastructure.
For North America, UL 67 configurations feature dead-front construction, approved circuit breakers, neutral and ground bars, and project-specific SCCR. For Europe and other markets, IEC 61439 configurations are available. Optional features include digital metering, SPD, circuit monitoring, and communication interfaces. NEMA-rated or IP-rated enclosures can be supplied according to regional and project requirements.
| 方面 | UL 67 Standard 技术选项 | IEC 61439-1/2 标准 技术选项 |
| 标准 | UL 67, CSA C22.2 No. 29, NEC (NFPA 70), IEEE | IEC 61439-1/2、IEC 60364、IEC 60909、IP防护等级 |
| 额定电压 | 600V、480V、415V、380V、240V、208V(最高可达1000V直流/交流) | |
| 额定电流 | 100A, 150A, 300A, 400A, 500A, 600A, 800A, 1000A, 1200A.. | 100A, 150A, 300A, 400A, 500A, 630A, 800A, 1000A, 1200A… |
| 频率 | 50Hz / 60Hz(兼容全球通用频率 (50/60Hz)) | |
| 系统类型 | 三相三线 (3P3W) / 三相四线 (3P4W) (可选中性母线(可提供带或不带中性线的配置)。 | |
| SCCR 和 ICW | 10kA, 35kA, (@415V/480V) | 10kA, 25kA, 35kA(@415V/480V) |
| 母线材料 | 镀锡/镀银铜(标准镀锡或镀银表面处理,具有优异的抗氧化性。) | |
| 外壳额定值 | 1号,3R号,4X号 | IP54、IP65 |
| 尺寸(高×宽×深) | 可变外壳尺寸,针对不同的电流额定值进行了优化。 | |
| 电缆入口 | 顶部和底部电缆入口或出口可定制,安装灵活。 | |
| 外壳材料 | 优质镀锌钢板。/ SS304不锈钢 | |
| 布雷克品牌 | Schneider、ABB、Eaton、Siemens、LS、Noark 或 KAILES 标准 | |
| 智能监控 | 带谐波分析和Modbus/TCP通信功能的智能电能表 | |
Provide the depth required by NEC Table 110.26(A)(1). The required depth is commonly 36, 42, or 48 inches, depending on voltage-to-ground and the condition opposite the panelboard.
Provide at least 30 inches (762 mm), or the width of the panelboard, whichever is greater. Doors and hinged panels must open at least 90 degrees.
Maintain at least 6 ft 6 in (1.98 m) of clear height, or the equipment height if greater. The highest circuit-breaker operating handle is generally limited to 6 ft 7 in (2.0 m).
Use a listed surface-mounted or flush-mounted configuration and secure it to a suitable structural wall. Front-access panelboards normally do not require a rear service aisle.
Reserve the panelboard footprint and the space above it to 6 ft above the equipment or the structural ceiling. Keep foreign piping and ducts outside this zone; compliant sprinkler protection may be permitted.
Keep the working area clear and accessible. Apply the correct NEMA enclosure for the location. Egress and panic-hardware requirements apply only when the equipment rating and room conditions trigger the applicable NEC requirements.
致力于为客户提供智能、安全、可靠的配电解决方案。